Visual 1 answers the reader's question directly: the dual-path control architecture, with the Nvidia-defined event/orchestration path across the top and customer-owned critical-safety actuation across the bottom. Boundary made explicit.
Visual 2 grounds the abstract boundary in physical geometry. The physical rack chassis and the logical control plane don't coincide. The shaded overlay makes that gap visible.
Both cite four verified Nvidia primary sources: DSX Exchange architecture + stateless async bus + NICo Key Capabilities + Mission Control 2.3 BMS-BCM integration.
Visual 1 · Dual-path control architecture
Two parallel sensor paths converge on NICo + Mission Control. Path A (Nvidia-managed) runs cold plate + inner-manifold sensors through the BMC. Path B (BMS-managed) runs facility-scale sensors through the customer BMS, exchanging events with NICo via DSX. Below NICo, three outputs: workload plane (health + allocation), compute-actuation plane (tray shutdown), event plane (BMS event exchange). Below the boundary line, customer-owned actuators — rack AC breaker, coolant valve, facility escalation.
Fanout geometry cleaned up: single stem from NICo, single horizontal branch at Y=306, three vertical drops into the outputs. No crossing lines.
Visual 2 · Physical boundary vs logical control plane
Same underlying architecture, grounded in the physical rack + facility topology. Two boundaries are drawn distinctly: the solid vermillion box is the physical compute-tray chassis (Nvidia's physical zone); the shaded vermillion overlay is the logical control plane, which extends beyond the chassis into BMS event ingest via DSX event exchange. Physical safety actuation (breakers, valves, facility escalation) stays outside the control plane, customer-owned.
The BMS is split into two sub-boxes to make the point precisely: the event-ingest side sits inside Nvidia's control plane (subscribed via DSX); the actuator side sits outside, driving breakers and valves per site-picked policy.
Addresses the "Nvidia = rack, customer = everything else" trap: the boundary is logical, not physical. The overlay makes visible that the control plane crosses the chassis.
Thesis to sharpen in §12
Current wording ("the response path and controls would continue to differentiate") is too broad for the level of Nvidia standardisation now on the record. New wording that survives the "Nvidia standardises everything" critique:
The sensor can standardise. The economic control point moves into the event, policy and workload response layers. Nvidia can standardise the event and orchestration path without owning the physical facility safety system.
Next step: confirm and I'll integrate Visual 1 as new Fig L4nv3 in §04c (or replace L4nv2), keep Visual 2 as an optional secondary in §04c, and tighten §12 in one PUT.